Maine’s Chewonki Foundation goes green

The ultimate display of sustainability is to educate the next generation. After all, it’s the younger set who’ll be more conscious of our finite resources than today’s consumers.


Wiscasset, Maine-based, nonprofit educational institution, the Chewonki Foundation, is doing just that. Nature-based courses are the majority of the curriculum, which can range from hour-long sessions to entire semesters. The Foundation took learning to a new level for the 40,000 students enrolled in any one of seven different courses.


The Foundation’s largest building, the Center for Environmental Education, received an interesting addition to its mechanical system last year. A portion of the building’s heating system was converted from fuel oil to an open-loop, water-to-water geothermal heat pump system. The retrofit is integrated with a data-logging unit which measures and records performance data.


The data, presented in a user-friendly format online, is available to Chewonki’s students and incorporated into many classes and demonstrations. The information, then, is transmitted to the Web by HOBOlink, a data-logging server. The geothermal retrofit is as much an ongoing experiment as it is a mechanical system upgrade.


The Maine Public Utilities Commission (MPUC) funded the project and insisted on data logging, hoping to gather impartial data on the efficiency of geothermal systems. The commission seeks hard information because managers there are actively researching the possibility of incorporating geothermal systems into public housing projects.


A link to the information can be found on the Foundation’s website (chewonki.org). The data, updated automatically every five minutes, is displayed in several forms, including a user-friendly line graph.


Building, naturally


The students at the Chewonki Foundation are immersed in nature nearly every waking minute, something that the Foundation feels is the very core of deep-seated respect for the natural world. But, when weather doesn’t permit outdoor learning, the two-story Center for Environmental Education is where the classes are held.


In addition to housing five large classrooms and staff offices, the building also has a 1,500-sq.-ft. meeting room, Chapin Hall, known affectionately as the “whale room,” stemming from the oddity of having a 30-foot finback whale skeleton suspended from the ceiling. It’s this room, with high ceiling and plenty of glass in two exterior walls that posed the greatest challenge to maintaining indoor comfort. That is, until the idea of a geothermal solution was raised.


And so, while the rest of the building’s heat is supplied by fuel oil, the whale room and its human occupants are heated by geothermal energy.


“Chapin Hall was chosen as the location of the experiment for two reasons,” said Peter Arnold, sus­tainability coordinator at Chewonki.


Arnold explained that the space is an ideally-sized heat load for the system (cooling in Maine was not a concern). Also, downstairs, the existing radiant heat manifold for Chapin Hall is located close to the geothermal heat pump, a three-ton Genesis system manufactured by ClimateMaster. “This helps visitors without a mechanical background see and understand the entire system,” added Arnold.


Mid Coast Energy Systems, based in Damariscotta, Maine completed the original, oil-fired mechanical system installation, as well as the geo retrofit. The 35-person company does installations and service in heating, plumbing, A/C, water treatment, geothermal, solar and IAQ.


According to John Blodgett, installation manager at Mid Coast, a staple-up, plated, pex radiant heat system was installed on the ground floor of the entire building when it was completed in ’98, including Chapin Hall. Heat comes from two oil fired boilers in the basement. The second floor is heated by convection baseboard.


On top of the Center building is a solar array, consisting of 42 PV modules, each producing 85 watts of power. What makes the array unique is its hybrid design. Under the panels is a Solarwall heat collector that preheats air going into the building’s ventilation system in the winter, and also strips heat off of the PV modules, making them more efficient.


Au naturale with geo


The ClimateMaster Genesis geothermal system was brought in to serve as the new, primary source of heat Chapin Hall’s radiant heat system, allowing MidCoast pros to deactivate the first connection between the well-insulated, under-floor PEX tubing network and the oil boiler. “We calculated and re-calculated the heat load for the Center and came up with a well-confirmed need for 36,000 BTUs on a design day of -10°F outdoor ambient,” said Dr. John Logan, regional director for Water Energy Distributors, Inc (WEDI). “The three-ton geothermal system was a perfect fit, down to the last BTU.”
According to Blodgett, they used several Taco components in the system, including the main and zone pumps. “We prefer Taco gear because of its proven reliability with us,” added Blodgett. “Precise flow control to the extensive, low-temp radiant heat system is a given with the right gear in place.”


The water-to-water geothermal heat pump provides mechanically-tempered heat to the meeting hall via eight, 300-foot, 1/2" pex radiant heat loops with flow through eight-port supply and return manifolds. The Genesis unit is connected to an open loop well with a depth of 325 feet, and a recharge rate of 25 gpm; more than adequate. “We’re very fortunate to be situated directly above a large aquifer, perfect for open-loop operation” said Arnold.


Water for the geo system’s thermal exchange is pulled from the ample supply in the well, used for geo-exchange, then discharged into a drain that spills into a wetland nature area in the center of the campus.
The pilot geo system, which has just completed its first heating season, produced about 14.5 million btus at an approximate cop of 4. As expected there were lessons learned. When the season’s data was collected the heat pump appeared to achieve a cop of 3 which was lower than expected. So the experts looked closely into the apparent disparity and found the answer: the btu meter was installed ahead of, rather than after, the heat pump. More recent, late-season calculations show the correct figure is a cop of 4, which will be verified next season with the meter in the correct location.


Refining the experiment


Two btu meters record btus extracted from the well water and btus sent to the floor. A kilowatt sensor measures the draw of all of the system pumps and circulators. Temperature probes measure the air inside and outside the structure, as well as the temperature of water going into and coming out of the ClimateMaster system.


The entire project was funded through a grant from the Maine Public Utilities Commission. In return, the Chewonki Foundation collected all data from the geothermal heating system through the heating season and made it available to the public. A report on the last season’s successful geothermal heating experience will be submitted to the MPUC shortly.


With so many smart people involved, it only makes sense that an intelligent system only gets smarter.